Revisions requested by inspectors:
Revision 1 - Replace emergency lights with new at lobby decorative ceiling, Specify lights in lobby decorative ceiling, Replace toilets with new, more efficient units - Water Wise Rebate Program
Revision 2 - Additional permit data/notes added (sheet A00), Install TV and associated receptacles in Boardroom
Revision 3 - Existing sanitary waste and roof drain cannot be relocated. In order to accommodate minor adjustments.
Revision 4 - Electrical conduits discovered in wall to remove. Opening adjusted to allow to remain. Soffit (initially called for removal) cannot be eliminated due to conflict with existing ductwork.
Revision 5 - Field inspector requested engineer drawings to cover the electrical adjustments. All work remains unchanged from the architectural plans. Only additional E-series sheets added to describe the work. (Existing vanity lighting in guestrooms need longer whip to install new fixture.
Revision 6 - Rooms 504, 506, 604 + 606 have an existing shower and will remain as-is. Revise (4) rooms (100, 110, 200 + 210) to keep as standard tub room.
Professionals on this permit LAND-RON, INC (Licensed Professional)
2026-08-20
Correction to the emergency light on the plans to match what was done in field - Reference Sheet A100 (New Ceiling Plan). We kept the surface mounted “bug eye” style emergency light and eliminated the 2 battery backup ceiling lights. Revision requested by inspector so we can get final electrical inspection.
Professionals on this permit ASSET SAFE INC (Licensed Professional)